渦街流量計(jì)的安裝主要從兩個方面考慮,第一是安裝點(diǎn)的選擇、第二則是是否安裝正確。若是這兩點(diǎn)有失誤或者錯誤,輕則影響測量精度,重則損壞流量計(jì)影響壽命。那么渦街流量計(jì)在直管段安裝有哪些要求呢?下面貝特小編就來給大家講解一下!
The installation of vortex flowmeter is mainly considered from two aspects, the first is the selection of the installation point, the second is whether the installation is correct. If there are errors or errors in these two points, the measurement accuracy will be affected, and the flowmeter will be damaged and the service life will be affected. So what are the requirements of vortex flowmeter installation in the straight pipe section? Let's explain it to you!
安裝直管段要求規(guī)范
Specification for installation of straight pipe section
1.安裝點(diǎn)上的上下游直管段一定的要求,否則會影響測量精度。
1. There are certain requirements for the upstream and downstream straight pipe sections on the installation point, otherwise the measurement accuracy will be affected.
2.安裝點(diǎn)上的上游有漸縮管,渦街流量計(jì)上游應(yīng)有不小于15D(D為管道直徑)的等徑直管段,下游應(yīng)有不小于5D的等徑直管段。
2. The upstream of the installation point has a tapered pipe, the upstream of the vortex flowmeter should have equal diameter straight pipe section of no less than 15d (D is the pipe diameter), and the downstream should be no less than 5D.
3.安裝點(diǎn)上的上游有漸擴(kuò)管,渦街流量計(jì)上游應(yīng)有不小于18D(D為管道直徑)的等徑直管段,下游應(yīng)有不小于5D的等徑直管段。
3. There is a diffuser upstream of the installation point. The upstream of the vortex flowmeter should have an equal diameter straight pipe section no less than 18D (D is the pipe diameter), and the downstream should be no less than 5D.
4.安裝點(diǎn)上游有90°彎頭或下行接頭,渦街流量計(jì)上游應(yīng)有不小于20D的等徑直管段,下游應(yīng)有不小于5D的等徑直管段。
The upstream and downstream pipe with straight diameter not less than 5D should be installed with straight pipe section not less than 5D.
5.安裝點(diǎn)上游在同一平面上有90°彎頭,渦街流量計(jì)上游應(yīng)有不小于25D的等徑直管段,下游應(yīng)有不小于5D的等徑直管段。
5. There are 90 ° elbows on the same plane upstream of the installation point. The upstream of vortex flowmeter should have no less than 25d equal diameter straight pipe section, and the downstream should have no less than 5D equal diameter straight pipe section.
6.流量調(diào)節(jié)閥或壓力調(diào)節(jié)閥盡量安裝在流量計(jì)下游5D以遠(yuǎn)處,若必須安裝在流量計(jì)的上游,流量計(jì)上游應(yīng)有不小于25D的等徑直管段,下游應(yīng)有不小于5D的等徑直管段。
6. The flow regulating valve or pressure regulating valve shall be installed at the distance of 5D downstream of the flowmeter as far as possible. If it must be installed at the upstream of the flowmeter, there shall be no less than 25d equal diameter straight pipe section in the upstream of the flowmeter, and the equal diameter straight pipe section not less than 5D in the downstream.
7.流量計(jì)上游若有活塞式或柱塞式泵,活塞式或羅茨式風(fēng)機(jī)、壓縮機(jī)。渦街流量計(jì)上游應(yīng)有不小于25D的等徑直管段,下游應(yīng)有不小于5D的等徑直管段。
7. If there are piston type or plunger type pump, piston type or roots type fan and compressor at upstream of flowmeter. There should be no less than 25d equal diameter straight pipe section upstream of vortex flowmeter, and no less than 5D equal diameter straight pipe section downstream.
上一篇: Principle, structure and installation of vortex flowmeter (system analysis)
下一篇: Application of pH controller in acid alkali automatic control
相關(guān)新聞
- Fault diagnosis and analysis of differential pressure transmitter in application 20-09-25
- Application and principle of bimetal thermometer 20-09-25
- How to install buoy level gauge 20-09-25
- Application of pH controller in acid alkali automatic control 20-09-25
- Cooling capacity measurement system of chilled water 20-09-25
- Advantage analysis of intelligent orifice flowmeter in actual measurement 20-07-29
- Problems encountered in operation of vortex flowmeter manufacturers 20-07-29
- Requirements for installation environment of vortex flowmeter 20-07-29